Appendix D: SNMP MIBS
52 ManageUPSNET User Instruction Manual
upsTest Group
(continued)
upsTestElapsedTime This object is updated while a test is in progress. Once a test is
complete, this object will contain the total elapsed time of the test
in 100ths of seconds.
upsWellKnownTests The OID values for the following objects are what the upsTestID
object is SET to in order to initiate a given test.
upsTestNoTestsInitiated If no tests are currently being run, then the value of upsTestId will
equal this OID.
upsTestAbortTestInProgress When running the upsTestDeepBatteryCalibration test, a delay of
up to 5 seconds can occur before the UPS returns to normal AC
operation.
upsTestGeneralSystemsTest Checks for error conditions that would also be displayed on the
front panel of the UPS.
upsTestQuickBatteryTest This test forces the UPS on battery for 15 seconds and is useful
for running a quick Pass/Fail test on the battery. Don't feel that you
have to periodically run this test though. The upsAlarmBatteryBad
alarm will automatically inform you when the battery is reaching
the end of its useful life. View this as a quick performance check.
upsTestDeepBatteryCalibration NOTE: This test discharges the battery to approximately 30% of its
capacity. It takes the UPS about three hours to fully recharge the
battery. Use this test with caution!
With this in mind, realize that this is a useful test. It truly tests the
battery capacity. Batteries used in all UPSs age and wear out. It is
suggested that this test be run no more often than once every
three months. It is possible to abort this (or any other) test by
writing the upsTestAbortTestInProgress OID to the
upsTestIdObject
upsConfig Group
The following objects in the UpsConfig Group are read-only. The read-only objects return the ratings of
the UPS.
UpsConfigInputVoltage
upsConfigInputFreq
upsConfigOutputVoltage
upsConfigOutputFreq
upsConfigOutputVA
Table 7. RFC1628 Support (Continued)