Appendix D: SNMP MIBS
56 ManageUPSNET User Instruction Manual
oneacUpsControl Group
(continued)
oneacUpsControlRemoteResetPassword This variable must be supplied with the SNMP adapter
access password in order to permit the SNMP agent to be
reset. This is the same password used for telnet access and
local serial port access via the MENU command. Note that
the remote access password must be changed from its
default value to work; using the default remote access
password is not permitted and will result in an error.
Any read of this object will return an empty string.
oneacUpsControlRemoteResetCommand Any positive value written to this object will cause the SNMP
agent to be reset. Note that this object requires the presence
of oneacUps ControlRemoteResetPassword in the same
SNMP message. Any read of this object will return a value of
0.
oneacUpsBattery Group
oneacUpsBattReplDate This object contains the date that the UPS batteries were last
replaced. When the UPS first leaves the factory, it is the same
as the UPS manufacture date.
oneacUpsNumBatt The number of battery packs attached to the extended
runtime power-head. If this UPS is not extendible then only a
value of 1 will be returned.
oneacUpsTest Group
oneacUpsTestId This variable functions in the same manner as the upsTestId
variable but does not require the management station
invoking the test to support the setting of the
upsTestSpinLock variable.
oneacUpsTestIndicators This test lights all of the front panel indicators as well as
turning on the buzzer if it was not previously disabled.
oneacUpsStatusGroup
oneacUpsUpTime The number of seconds the UPS has been running since the
UPS was last reset. oneacUpsFrontPanelDisplay The current
front panel display on the UPS.
oneacUpsMinVolts The lowest input voltage value seen since the last reset.
Setting this object to 0 will cause both oneacUpsMinVolts and
oneacUpsMaxVolts to be reset to the current input voltage.
oneacUpsMaxVolts The highest input voltage seen since the last reset. Setting
this object to 0 will cause both oneacUpsMinVolts and
oneacUpsMaxVolts to be reset to the current input voltage.
Table 8. Private Extension MIB